Star-delta starter with a timer

A star-delta starter (wye-delta starter) reduces the starting current of a three-phase induction motor. The motor starts with its windings in star, so each winding gets only 1/√3 of the line voltage (230 V instead of 400 V). After a few seconds a timer switches it to delta, where each winding gets the full 400 V and the motor gives its full torque. In star, the starting current and the starting torque are both about one third of a direct-on-line start.

This tutorial builds the complete circuit in Virtuino Circuits, with the power circuit, the control circuit and a timer, and then simulates the changeover. You need a motor with six terminals (U1 V1 W1, U2 V2 W2), rated 400 V in delta (marked 400/690 V on the nameplate).

Open the ready-made circuit in the simulator

The three contactors

ContactorRoleWhen it is closed
K1 main (line)Feeds U1, V1, W1 from L1, L2, L3For the whole run
K2 starConnects U2, V2, W2 together (star point)Only during the start
K3 deltaConnects U2, V2, W2 to the lines, closing the deltaAfter the timer, until stop

K2 and K3 must never close together: that would short-circuit the three phases. They are interlocked electrically, exactly like the forward/reverse circuit.

Part 1: the power circuit

  1. Supply and protection. Place L1, L2, L3 and PE, then a 3-pole MCB or fuses Q1 for short-circuit protection.
  2. Main contactor K1. Place 3-pole main contacts named K1. Its outputs go to a thermal overload relay F2 and then to U1, V1, W1 of motor M1. Choose the three-phase motor with 6 terminals.
  3. Delta contactor K3. Place main contacts named K3. Feed its inputs from the same three lines after Q1, and connect its outputs so that the delta closes: L1 → W2, L2 → U2, L3 → V2.
  4. Star contactor K2. Place main contacts named K2. Connect its inputs to U2, V2, W2 and connect its three outputs together. This is the star point.
  5. PE. Connect the motor's PE terminal.
Overload setting. With the thermal relay in the motor lines after K1 (as here), it carries the winding current, not the line current. Set it to 0.58 × the rated motor current (1/√3). If you place it before K1, in the line, set it to the full rated current.

Part 2: the control circuit

  1. Supply. L1 → control circuit breaker F3 (1-pole) → overload contact F2 95-96 (NC) → stop button S0 (NC).
  2. Start and main contactor. Start button S1 (NO), in parallel with the holding contact K1 23-24. After them place the coil K1 to N.
  3. Timer. In parallel with coil K1 (same two nodes), place an on-delay timer coil (TON) named KT1, from Relays, timers and contactors. Set the time to 5 s in its properties. KT1 stays energised as long as K1 is on.
  4. Changeover contact. From the node after S1/K1, place the delayed changeover contact of KT1: common 15, delayed-opening NC 16 and delayed-closing NO 18.
  5. Star branch. 16 → an NC contact K3 (21-22, interlock) → coil K2 to N.
  6. Delta branch. 18 → an NC contact K2 (21-22, interlock) → coil K3 to N. No holding contact is needed, because KT1 keeps its contact changed over until Stop.
  7. Check. Run the design check and fix any unconnected terminal.

Simulate the changeover

  1. Press F5 and click S1. K1, KT1 and K2 energise: the motor starts in star. The motor symbol shows the star connection and the direction of rotation.
  2. Watch the timer. After 5 s its contact changes over: 15-16 opens and K2 drops out, 15-18 closes and K3 pulls in once the interlock K2 21-22 has closed again. The motor now runs in delta.
  3. Use the speed buttons (×10, ×60) on the floating bar if you set a long time.
  4. Click S0: everything drops out and the timer resets.

Why the motor must be 400 V in delta

In delta, each winding is connected between two lines and gets 400 V. A motor marked 230/400 V is designed for 230 V per winding, so on a 400 V network it can only run in star and cannot be started star-delta. You need a 400/690 V motor. In the simulator, a winding with too high a voltage is reported as overvoltage.

Choosing the timer

The star time should be long enough for the motor to reach about 80–90 % of its speed, usually 3–10 s depending on the load. If you switch to delta too early, the current peak is almost as high as a direct start. Some starters also add a short pause (about 50 ms) between star and delta so that the arc of K2 is extinguished before K3 closes.

Next steps

Open this circuit in the simulator