Forward / reverse motor control with interlocking
A reversing starter lets a three-phase motor run in both directions. Two contactors are used: K1 for forward and K2 for reverse. K2 swaps two of the three phases, so the rotating field and the shaft turn the other way. The most important part of the circuit is the interlocking: K1 and K2 must never be closed at the same time, because that would short-circuit two phases.
In this tutorial you draw the power circuit and the control circuit in Virtuino Circuits, then simulate them: you will see the motor change direction, and what happens when the interlock is missing. It takes about 20 minutes and builds on the self-holding circuit.
Open the ready-made circuit in the simulator
How the circuit works
- S1 (forward) energises K1, which holds itself through its contact 13-14.
- S2 (reverse) energises K2, which holds itself the same way.
- S0 (stop, NC) is in series with both branches and stops the motor in either direction.
- A normally closed contact of K2 (21-22) is in series with the coil of K1, and a normally closed contact of K1 is in series with the coil of K2. While one contactor is energised, its NC contact is open, so the other coil cannot be energised. This is the electrical interlock.
- The overload contact 95-96 of the thermal relay (or the auxiliary contact of a motor protection breaker) opens both branches on overload.
Part 1: the power circuit
- Supply. Open the app and start a blank drawing. From Supply place L1, L2, L3 and PE at the top of the sheet (400 V, 50 Hz).
- Protection. From Protection place a motor protection breaker Q1 under the three phases (or a 3-pole MCB plus a thermal overload relay F2). Set the rated current close to the motor current.
- Forward contactor. From Relays, timers and contactors place a 3-pole set of contactor main contacts and name it K1. Wire L1, L2, L3 straight through: input 1-3-5, output 2-4-6.
- Reverse contactor. Place a second set of main contacts named K2 next to K1. Feed its inputs from the same three lines, but cross two phases at the output: L1 goes to the terminal that K1 feeds with L3, and L3 to the terminal that K1 feeds with L1. L2 stays in the middle.
- Motor. From Loads place a three-phase motor M1 and connect U1, V1, W1 to the common outputs of K1 and K2. Connect its PE terminal to PE.
Part 2: the control circuit
Use 230 V AC from L1 and N (or 24 V DC from L+ and M, with 24 V coils). The control circuit is drawn vertically, with two branches side by side.
- Control fuse. Place L1 at the top, then a fuse F3 (for example 2 A).
- Overload contact. Place the NC auxiliary contact 95-96 of the thermal relay F2 (or the auxiliary contact of Q1) in series.
- Stop. Place push button S0, type NC. Everything after S0 can be switched off by it.
- Forward branch. Under S0, place push button S1 (NO), with an auxiliary contact NO named K1 (13-14) in parallel. Below them, an auxiliary contact NC named K2 (21-22), and then the coil K1. Wire the coil to N.
- Reverse branch. From the node after S0, draw the mirror branch: S2 (NO) in parallel with K2 13-14, then an NC contact named K1 (21-22), then the coil K2 to N.
- Indicator lamps (optional). Add lamp H1 through a K1 NO contact and lamp H2 through a K2 NO contact, so you can see the direction from the panel door.
- Check. Click the design check button. It reports unconnected terminals and duplicate designations before you simulate.
Simulate it
- Press
F5. Click S1: K1 pulls in and holds itself, the motor turns forward, H1 lights. - Click S2 while the motor runs forward. Nothing happens: the open NC contact K1 21-22 blocks coil K2. The interlock works.
- Click S0, then S2: K2 pulls in, the motor turns in reverse, H2 lights.
- Remove the interlock: delete the NC contact K1 from the reverse branch and replace it with a wire. Start the simulation, run forward, then press S2. Both contactors close, L1 and L3 are shorted through the main contacts, and the protection trips. The simulator reports the short circuit and which phases were involved. Put the interlock back.
- Try an overload: increase the motor load or lower the overload setting. The thermal relay heats up along its curve and trips; its 95-96 contact stops the motor.
Push button interlocking (double interlock)
Many panels also interlock the buttons. Use NO+NC push buttons: the NC contact of S2 is placed in series in the forward branch, and the NC contact of S1 in the reverse branch. Pressing the other direction button then first drops the running contactor and then starts the other one, without pressing Stop. The electrical interlock with the contactor NC contacts must stay, because it also protects against a welded or stuck contactor.
Common mistakes
- Swapping the phases at the input of K2 instead of the output, or swapping all three phases.
- Putting the interlocking NC contact of the same contactor (K1 21-22 in the K1 branch). The coil then switches itself off.
- Placing the holding contact in parallel with S0 as well: Stop can no longer stop the motor.
- Forgetting the overload contact 95-96 in the control circuit, so the thermal relay trips without stopping the contactor.
Next steps
- Star-delta starter with a timer: reduce the starting current of a large motor.
- The same forward/reverse circuit on a PLC, with the interlock in Ladder.