Star-delta starter on a PLC with a TON timer

The relay star-delta starter uses a timer relay to switch the motor from star to delta. On a PLC the timer is an instruction: TON (on-delay timer). This tutorial programs the full sequence on a Siemens S7-1200 in Virtuino Circuits, including a short pause between star and delta, which is hard to do with relays but easy in a PLC.

Open the ready-made circuit in the simulator

I/O list

AddressDevice
%I0.0S0 Stop (NC)
%I0.1S1 Start (NO)
%I0.2F2 Overload 95-96 (NC)
%Q0.0K1 Main contactor
%Q0.1K2 Star contactor
%Q0.2K3 Delta contactor

Wiring

  1. Draw the power circuit of the star-delta starter: K1 to U1 V1 W1 through the overload relay, K3 to W2 U2 V2, and K2 as the star point. Use the 6-terminal three-phase motor.
  2. Place the PLC (S7-1200 CPU 1214C), supply it from L1/N and wire the inputs from 24 V DC.
  3. Wire the outputs: .0 → coil K1 → N; .1 → coil K2 → K3 21-22 → N; .2 → coil K3 → K2 21-22 → N. The NC contacts are the hardware interlock between star and delta.

Ladder program

 Rung 1 – Main contactor (start/stop with seal-in)
      %I0.1        %I0.0   %I0.2                       %Q0.0
 |-----| |---+------| |-----| |-------------------------( )---|
      %Q0.0  |
 |-----| |---+

 Rung 2 – Star time
      %Q0.0                         T1: TON  PT = 5 s
 |-----| |---------------------------[IN          Q]-------|

 Rung 3 – Changeover pause
       T1                           T2: TON  PT = 0.1 s
 |-----| |---------------------------[IN          Q]-------|

 Rung 4 – Star
      %Q0.0    T1     %Q0.2                            %Q0.1
 |-----| |-----|/|-----|/|------------------------------( )---|

 Rung 5 – Delta
      %Q0.0    T2     %Q0.1                            %Q0.2
 |-----| |-----| |-----|/|------------------------------( )---|
  1. Rung 1 is the start/stop seal-in for the main contactor.
  2. Rung 2. From the timers group place a TON. In its properties give it the name T1 and PT = 5 s. Its input is the main contactor output. While K1 is on, T1 counts; after 5 s its output Q becomes 1.
  3. Rung 3. A second TON named T2, PT = 0.1 s, started by a contact T1. Contacts with a timer's name follow its output Q.
  4. Rung 4. Star = main on AND T1 not yet done AND delta off.
  5. Rung 5. Delta = main on AND T2 done AND star off.
Why the pause? Inside one PLC scan, rung 4 switches star off and rung 5 could switch delta on immediately. Real contactors need a few tens of milliseconds to open and extinguish the arc. If K3 closed while K2 was still arcing, there would be a phase-to-phase short circuit. T2 gives K2 100 ms to open first. The hardware interlock is still needed as a second barrier.

Simulate

  1. Press F5 and open the Ladder window. Click S1.
  2. K1 and K2 pull in, the motor starts in star. In the Ladder window the TON box shows the elapsed time ET counting up to 5 s.
  3. At 5 s, star drops out; 0.1 s later delta pulls in. The motor symbol changes from star to delta.
  4. Press S0: all outputs go off and both timers reset to 0, ready for the next start.
  5. Use ×10 on the floating bar to speed up the clock, or set a longer PT to watch the changeover slowly.