Analog signals

Analog signals are 0–10 V. Analog wires are drawn in orange. The value of a potentiometer or transmitter is set in simulation with a large slider (click the symbol).

Sources

  • Potentiometer: connected between two potentials; the wiper gives a fraction of the end voltage (for example 0–10 V between L+ and M of a 10 V supply, or 0–24 V on a 24 V supply).
  • Transmitter 0–10 V, 3-wire (L+, U, M): measures temperature, pressure, level, flow or distance with a configurable range and unit; needs 15–30 V DC and outputs 0–10 V proportional to the value.

PLC analog inputs

Each model converts 0–10 V to its own raw value, shown live next to the input in simulation:

ModelRaw rangeAddress
S7-12000…27648 (overflow 32767 above 11.76 V)%IW64, %IW66
S7-2000…32000AIW0
LOGO! 12/24, M2210…1000AI1–AI4, %IW0.0
Generic PLC0…27648 (configurable)IEC style

SCALE and UNSCALE

In Ladder, SCALE converts a raw analog input into an engineering value with a name (for example TEMP, 0…100 °C) that comparisons can use: OUT = MIN + IN / RAW_MAX · (MAX − MIN). UNSCALE does the opposite: it takes a value or a name (for example a set-point 0…100 %) and writes the raw value to an analog output. Together they let a potentiometer set the speed of a motor through the PLC.